SKM Apcy H APCY5300DH

SKM

SKM Apcy H APCY5300DH

Chiller

AvailabilityMade to orderLead time 13 weeks
Nominal cooling capacity
1072kW
Cooling capacity at T3 (46 °C)
988.6kW
Power input (cooling)
319.8kW
Rating standard
Ahri 550 590
Climate class
T3
EER (standard condition)
3.354
Henrik

Henrik can take it from here.Sizing, pairing, budget price and lead time to your site.

Technology byNexoMind

Prices are not shown online. Henrik and the team quote them, excluding VAT.

Technical data

Capacity

Nominal cooling capacity
1072 kW
Cooling capacity at T3 (46 °C)
988.6 kW
Power input (cooling)
319.8 kW
Rating standard
Ahri 550 590
Climate class
T3

Efficiency

EER (standard condition)
3.354
IPLV
4.364

Refrigeration

Refrigerant
R134a
Compressor type
Screw
Number of compressors
2
Refrigerant circuits
2

Hydronic

Water flow
51.31 l/s
Water pressure drop
29.0 kPa
Entering water temperature
12 °C
Leaving water temperature
7 °C

Chiller

Chiller type
Air cooled
Evaporator type
Shell and tube

Electrical

Nominal voltage
380 V
Power supply
Three
Frequency
50
Rated current
556 A
Minimum circuit ampacity (MCA)
913 A

Acoustics

Sound pressure
80.3 dB(A)
Sound power
99.5 dB(A)

Operating envelope

Min outdoor temperature (cooling)
-4 °C
Max outdoor temperature (cooling)
52 °C

Physical

Height
2708 mm
Width
2242 mm
Depth
9507 mm
Weight
9817 kg

Compliance & certifications

Certifications
Ahri certified, Iso 9001, Iso 14001

Suitability

Used in / applications
Hotel hospitality, High rise, Retail, Healthcare, Warehouse industrial, Rooftop outdoor

Commercial

Warranty
2 years
Country of origin
United Arab Emirates

From the manufacturer's published documentation. Confirm selection data against the current datasheet before specification.